Application:
1. Can be used in Zone 1 and Zone 2 dangerous places.
2. Can be used in II A、II B、II C explosive atmosphere.
Mode implication
Feature
1. Die-casted shell of ZL102 Aluminum alloy with high-pressure electrostatic plastic-sprayed surface, stainless steel outer fixed parts.
2. Inside is installed AC contactor, thermal relay, self-settable conversion switch.
3. Able to directly control AC 50Hz, 380V asynchronous motor with the protection of overload, phase-failure and voltage-absent.
4. Suitable for steel pipe and cable wiring.
5. Suitable for Gb3836, IEC60079 standard.
Main technical parameters:
1. Ex-mark: Exde ⅡB T4 Gb/Exde ⅡC T5 Gb/Ex tD A21 IP65 T130℃/Ex tD A21 IP65 T95℃
2. Protection grade: IP54/IP65
3. Corrosion-proof grade: WF1
4. Mounting way: Pendant type
5. Rated voltage: AC380V
6. Rated current: Maximum current 63A
Reversible current: Maximum curren 40A
7. Power: Maximum power: 30kW, Reversible power: 18.5kW
8. Current range: 0.25~70A
9. Ingress thread specification: G1" , G1 / "
10. Ingress cable’s outer spcification:φ14mm~φ17mm,φ26mm~φ32mm
*Note: If the current is up to the technical parameters, please contact with the engineer and technician dept.
Electric principle chart Outline example
|